Protectowire 2000 FireSystem Manuel d'utilisateur Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 33
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
9
adjacent branch line and proceeds in the opposite
direction. The detector run continues in this
manner until the end of the detection zone is
reached, or until the maximum Protectowire con-
trol panel zone allocation is reached, typically
5,000 feet [1,524 m].
The completed Protectowire portion of the
circuit for each overhead zone will be in a ser-
pentine pattern as illustrated in Figure 6, with
the Protectowire terminated at each end in an
approved zone box, end-of-line zone box, or
other approved junction box provided as part
of the system. Strain relief connectors, Series
SR-502, shall be installed in all junction boxes
where Protectowire enters or exits the enclo-
sure, in order to hold the cable securely and
maintain dust and moisture tight conditions.
(See Figures 1, 1A, 1B).
Detector Zoning For Sprinkler Release
Detection system zone allocation should not
be confused with zone allocation for sprin-
kler systems. A water system, or sprinkler
zone controlled by one valve may have a dif-
ferent meaning than terminology used for
detection zones. Generally, a detection zone
refers to a defined area within a protected
premise. In the case of Protectowire, it also
refers to the maximum amount of linear heat
detection cable that a panel will operate on a
single detection circuit (zone). Protectowire
panels such as the FS2000, SRP-4x4, and 2600
HD Series are approved for 5,000 feet
(1,524 m) per zone.
On the other hand, a water zone, or system,
has an area of coverage based upon its
designed discharge density which may exceed
the area which can be covered effectively by a
single detection zone. When a detection zone’s
length limitation is exceeded, a second detec-
tion zone is required to complete the total area
of detector coverage needed to match the area
of coverage provided by the corresponding
water zone. In this scenario, the two detection
zones are connected at the control panel in an
“or configuration so that the actuation of
either detection zone will operate the
solenoid of the corresponding water
system. Do not extend a detection circuit
from one area into an area serviced by
another water valve. Each water valve must
be controlled by one or more detection
zones physically located in the same area.
Rack systems - With the variety of rack sys-
tems in use today, a wide range of configu-
rations may be confronted when installing
linear heat detection systems for electrical
actuation of sprinkler valves. As a mini-
mum, the guidelines of Factory Mutual in
conjunction with the manufacturer’s rec-
ommendation must be followed. In general,
rack detection systems should be installed
based upon the following criteria:
For single row and double row racks, one
line of detection cable is needed at each in-
rack sprinkler level. Locate the linear heat
detector cable in the transverse or longitu-
dinal flue space and attach it to a horizon-
tal load beam at the sprinkler line level.
For multiple-row racks, a line of detection
cable is needed for each in-rack sprinkler
line at each in-rack sprinkler level. Locate
the linear heat detection cable in either the
transverse or longitudinal flue space and
attach it to a horizontal load beam at the
sprinkler branch line levels.
EEnnvviirroonnmmeennttaall
CCoonnssiiddeerraattiioonnss
Protectowire is available in a range of con-
structions and jacket materials, in order to
provide resistance to attack from various
,
Figure 6
Vue de la page 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 32 33

Commentaires sur ces manuels

Pas de commentaire